Deltabar M 5x



Version

1



Registered Product Information

Manufacturer: Endress+Hauser
Product Name: Deltabar M 5x
Product Description: Differential Pressure Transmitter
Profile: FOUNDATION Field Device
More Information:   Deltabar M 5x with silicon sensors * Measurement of flow, level or differential pressure of gases, vapors and liquids * Measuring spans from 0.4 inH2O to 580 psi (1 mbar to 40 bar) * Nominal pressure up to 2300 psi (160 bar) * Suitable for use in hazardous areas Features and Benefits: * High long term stability * High accuracy - accuracy better than 0.1% of set span - optional "platinum" version, accuracy better than 0.075% of set span * Turn down20:1, higher on request * Meets PED (Pressure Equipment Directive) * Function-monitored from the measuring cell to the electronics * Process temperatures up to 185°F (85°C) as standard * Compact design and universal modularity for differential pressure and gauge/absolute pressure (Deltabar M and Cerabar M), i.e. replaceable display, universal electronics for gauge/absolute pressure and differential pressure * Simple and easy operation via 4 to 20 mA, HART® protocol or connection to Profibus-PAor Foundation Fieldbus * Zero and span freely adjustable with or without reference pressure * Wide variety of software functions such as diagnostics, simulation, linearization curves, totalizer, etc. 

Registered Product Details

Manufacturer ID (hex): 452B48
Device Type ID (hex): 1021
DEV_REV (hex): 01
DD Revision: 0x03(DD4), 0x03(DD5), 0x02(CF)
FOUNDATION Physical Layer Profile: 111 - Standard-power signaling, bus-powered, Entity Model I.S. 511 - Low-power signaling, bus-powered, FISCO I.S.
Stack Manufacturer: Endress+Hauser Process Solution AG
FOUNDATION Stack Class: 31PS, 32LT
Stack Version: 4.0
Registered Blocks: 1-RB2(e), 2-AI(e), 1-DI(s), 1-DO(s), 1-IS(s), 1-PID(s), 1-AR(s), 1-SC(s), 1-IT(s), 1-PTB(e)
Other Blocks: 1-Diagnostic(c), 1-DISP(c), 1-DPFLOW(c)
Registered Features: Alarms and Events Function Block Linking Trending Block Instantiation

Registration Information

Registration Authority: FieldComm Group
Registration Status: Registered
Tester Version: 5.2.0
DD/CFF Tester Version: 5.2.0

Contact Information

Device Support File Usage

FieldComm Group (FCG) makes available to its members and to the public certain device driver (DD) files, in various forms, that have passed certain tests conducted by or through FCG. The DD files are, or are created from, submissions to FCG by FCG members and are provided by FCG AS IS. FCG disclaims all liability for the accuracy, suitability or use of the DD files. Each member creating DD files has its own policies regarding supporting use of those files, and may, for instance support use of DD object code files, but not DeviceInfo or other files. While FCG is under no obligation to provide support for use of any DD files, FCG welcomes all inquiries on the subject and will often be able to assist.